M2 Setpoint generator 96 x 48 mm

Montwill Produkte: M2 Setpoint generator 96 x 48 mm

Item description

The M2-1GR5B.00X0.570xD is a 5-digit display for the output of direct current/direct voltage signals for setpoint setting and a
visual limit value monitoring. The configuration happens via 4 front keys or via PM-TOOL, our optional PC-software. The integrated direct voltage output serves as contact supply for key switches or external navigation keys. Optionally, two switching points are available. Selectable software functions, a direct limit value adjustment in operating mode, as well as the compact
installation depth of 89 mm create a solid device concept.

M3 Setpoint generator 96 x 48 mm with Profibus DP

Montwill Produkte: M3 Setpoint generator 96 x 48 mm with Profibus DP

Item description

The M3-1GR5B.9000.W70xD is a 5-digit display for the output of direct current/direct voltage signals for setpoint setting and a
visual limit value monitoring and a setpoint query via Profibus DP. Configuration happens via 4 front keys or via PM-TOOL, our optional PC-software. The integrated direct voltage output serves as contact supply for key switches or external navigation keys. Many selectable software functions, a direct limit value adjustment in operating mode, as well as a compact installation depth of 139 mm create a solid device concept.

Montwill Produkte:

Item description

Montwill Produkte:

Item description

Technical Data

Housing 96 x 48 mm
Display 5-digit
14 mm digit height
Colour: red, green, orange or blue display
Range displayed -19999 to 99999
Operation front panel keyboard protection class IP65
Input 2 digital inputs: < 2.4 V OFF; 10 V ON; max. 30 VDC
Analogue Output 0/4-20 mA / 0-10 VDC / 16 Bit
Switch point 2 relays (change-over contact)
250 V / 5 AAC, 30 V / 5 ADC
Interface
Power supply 230 VAC
10-30 VDC
Sensor supply 15 VDC / 10 mA
Software properties
  • definable setting range for the setpoint
  • configurable output area between 0-10V and 0/4-20mA
  • adjustable step size per keystroke
  • display flashing at threshold value exceedance/undercut
  • digital input for key switch or external adjustment keys
  • zero-key for a fast recall of a default value
  • configurable code as adjustment protection for the setpoint
  • different operating options for the setpoint adjustment
  • start behaviour with last setting value or default value
  • speed levels for the behaviour of the setpoint
  • fast reaction for adjustment of the setpoint value (Ramp function)
  • programming interlock via access code
Downloads Data sheet and price list
Manual